Run a correspondence check
A correspondence check compares the architecture model with the structure model, object by object. It finds load-bearing elements that are in one model but missing in the other, and elements that are in both but do not match in size or position.
Before you start
- Models: one architecture model and one structure model in the project, with the right disciplines. The architecture side takes the disciplines Architecture, Facade, Interior and Opening; the structure side takes Structure, Steel Structure, Prefab Concrete and Structural Timber. See Manage models.
How the comparison works
The architect and the structural engineer each model the same walls, slabs, columns and beams. SiloLink compares them by volume: for every object it looks for the objects of the other model that take up the same space, and measures how much of the volume they share.
- Matched: the objects share at least the volume threshold of their volume, 80% by default. They correspond.
- Unmatched: the objects overlap, but share less than the threshold. For example, the structural column is longer than the architectural one, or a wall is thicker in one model.
- Missing: the object has no counterpart in the other model at all.
One object can correspond to several, for example one architectural wall to three structural wall segments. They are compared as a group, and each object in it must still share at least 50% of its volume. Objects whose geometry is missing or faulty, or whose comparison was inconclusive, are listed as Unresolved instead.
1. Set up the check
Open Checks, click New and choose Correspondence checking.
- Check scope (1): pick the architecture model and the structure model and their versions. Tick views to compare only the objects they show.
- Object types (2): the IFC classes to compare. Walls, slabs, columns and beams are ticked by default.
- Grouping method (3): how results are grouped for review: Discipline + object types, Discipline + object types + levels, or Spatial distance.
- Algorithm settings (4):
- Cross-type matching: on, objects of different types may match, for example an architectural wall with a structural wall element. Off, only objects of the same family can form a pair. The volumes must match either way.
- Volume threshold: how much of the volume must be shared for a match. Higher is stricter; 80% is the default.
- Prefix (5): a short code for this check. It is used in the check's name and in the title of its issues; see Use the prefix.
- Click Start (6). Tick Email me when this run finishes to get an email.