Clash detection with views
Check exactly the objects that matter by using as the detection source. A typical example: the load-bearing elements of the architecture and structure models against the whole HVAC model. Ducts and pipes that run into light partitions, doors or furniture are then left out, and the review focuses on clashes with the structure.
Before you start
- Views: the views you want to check exist in the project. Every project has example views, such as Load-bearing elements in Examples: Filters. To make your own, see Use views.
1. How views and models add up
A view in the detection source adds the objects it shows, transparent ones included. Ticked models add all their objects. SiloLink checks the sum of both.
| You tick | SiloLink checks |
|---|---|
| The Load-bearing elements view | The load-bearing walls, columns, beams and slabs of every model the view covers |
| The HVAC model | Every object of the HVAC model |
| Both | Both sets of objects, each against the other and against itself, as the clash matrix allows |
2. Choose views and models
- Start a new clash check: Checks › New › AI clash review (matrix).
- Under Detection source, open Views and its folder, and tick the views (2). Here: Load-bearing elements.
- Tick the models that should be checked whole (1). Here: HVAC. Architecture and Structure show a partly ticked box, because the view brings only some of their objects.
- The viewer (3) shows exactly the selected objects. Check that they are what you want before you go on.
3. Check the clash matrix
Click Configure matrix. The matrix now holds only the object types of your selection (1): here 12 object types and 66 pairs, instead of 30 types and 300 pairs for the full models.
- The load-bearing types (2) come from the view: walls from Architecture, beams, columns and slabs from Structure.
- The HVAC types (3) come from the whole HVAC model.
Turn off pairs you do not need, for example HVAC against HVAC if you only care about clashes with the structure. Then click OK.
4. Finish and start
Set grouping, severity and issues as usual, and click Start. See Run a clash check.